Rheological Characteristics and Optimization of Novel TiO2-POE Nanolubricant Using Response Surface Method (RSM) for Air Conditioning System Compressor Application

This study aims to determine the viscosity characteristics of TiO2-Polyolester (POE) nanolubricant and optimize it for heat transfer applications in compressor air conditioning systems. A magnetic stirrer was used to mix TiO2 and POE lubricant for 30 min. The nanolubricant was then ultrasonicated wi...

Description complète

Détails bibliographiques
Auteurs principaux: Nugroho, Agus, Rizalman, Mamat, Bo, Zhang, Wan Hamzah, Azmi, Mohd Fairusham, Ghazali, Yusaf, Talal
Format: Conference or Workshop Item
Langue:English
English
Publié: Springer Singapore 2023
Sujets:
Accès en ligne:http://umpir.ump.edu.my/id/eprint/34980/7/Rheological%20Characteristic%20and%20Optimization%20of%20Novel1.pdf
http://umpir.ump.edu.my/id/eprint/34980/13/Rheological%20Characteristics%20and%20Optimization%20of%20Novel%20TiO2-POE%20Nanolubricant%20Using%20Response%20Surface%20Method%20%28RSM%29%20for%20Air%20Conditioning%20System%20Compressor%20Application.pdf
Description
Résumé:This study aims to determine the viscosity characteristics of TiO2-Polyolester (POE) nanolubricant and optimize it for heat transfer applications in compressor air conditioning systems. A magnetic stirrer was used to mix TiO2 and POE lubricant for 30 min. The nanolubricant was then ultrasonicated with a probe for 120 min to stabilize the TiO2-POE nanolubricant. There were seven different types of samples examined in this study, with concentrations of 0, 0.05, 0.15, 0.25, 0.35, 0.45, and 0.85 vol%. Rotational Rheolab QC was used to quantify viscosity from 30 to 90 °C. The viscosity of nanolubricant augmented as the proportion of nanolubricant increased. In contrast, when the test temperature rises, the viscosity drops. The greatest viscosity rise was 56.657% at 0.85 vol% at 80 °C, while the lowest viscosity increase was 0.029% at 0.05% at 30 °C. Based on the Response Surface Approach, optimization using the Multivariable Functions Optimization (MBFO) method with the Central Composite Design (CCD) type. The uncertainty analysis was also performed in this study. The most optimum dynamic viscosity is 34.8098 mPa s. At a temperature of 60 °C, this condition was achieved in samples with a concentration of 0.45 vol%.