Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids
On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances o...
Main Authors: | , , , , , , , , , , , , , , |
---|---|
Format: | Article |
Language: | English |
Published: |
MDPI AG
2023-07-01
|
Series: | Sensors |
Subjects: | |
Online Access: | https://www.mdpi.com/1424-8220/23/14/6317 |
_version_ | 1797587488785563648 |
---|---|
author | Fernando Garnacho Fernando Álvarez Alf-Peter Elg Christian Mier Kari Lahti Abderrahim Khamlichi Eduardo Arcones Joni Klüss Armando Rodrigo Mor Pertti Pakonen José Ramón Vidal Álvaro Camuñas Jorge Rovira Carlos Vera Miran Haider |
author_facet | Fernando Garnacho Fernando Álvarez Alf-Peter Elg Christian Mier Kari Lahti Abderrahim Khamlichi Eduardo Arcones Joni Klüss Armando Rodrigo Mor Pertti Pakonen José Ramón Vidal Álvaro Camuñas Jorge Rovira Carlos Vera Miran Haider |
author_sort | Fernando Garnacho |
collection | DOAJ |
description | On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270. |
first_indexed | 2024-03-11T00:40:38Z |
format | Article |
id | doaj.art-0141dcf4dab8410aa9cd667bad49a169 |
institution | Directory Open Access Journal |
issn | 1424-8220 |
language | English |
last_indexed | 2024-03-11T00:40:38Z |
publishDate | 2023-07-01 |
publisher | MDPI AG |
record_format | Article |
series | Sensors |
spelling | doaj.art-0141dcf4dab8410aa9cd667bad49a1692023-11-18T21:16:02ZengMDPI AGSensors1424-82202023-07-012314631710.3390/s23146317Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC GridsFernando Garnacho0Fernando Álvarez1Alf-Peter Elg2Christian Mier3Kari Lahti4Abderrahim Khamlichi5Eduardo Arcones6Joni Klüss7Armando Rodrigo Mor8Pertti Pakonen9José Ramón Vidal10Álvaro Camuñas11Jorge Rovira12Carlos Vera13Miran Haider14Fundación para el Fomento de la Innovación Industrial, FFII-LCOE, Eric Kandel Street 1, Getafe, 28906 Madrid, SpainDepartment of Electrical and Electronic Engineering, Automatic Control and Applied Physics, School of Industrial Design and Engineering (ETSIDI), Universidad Politécnica de Madrid (UPM), Ronda de Valencia 3, 28012 Madrid, SpainRISE Research Institutes of Sweden, 501 15 Borås, SwedenDelft University of Technology, Mekelweg 4, 2628 CD Delft, The NetherlandsDepartment of Electrical Engineering, Tampere University (TAU), Korkeakoulunkatu 3, 33720 Tampere, FinlandFundación para el Fomento de la Innovación Industrial, FFII-LCOE, Eric Kandel Street 1, Getafe, 28906 Madrid, SpainDepartment of Electrical and Electronic Engineering, Automatic Control and Applied Physics, School of Industrial Design and Engineering (ETSIDI), Universidad Politécnica de Madrid (UPM), Ronda de Valencia 3, 28012 Madrid, SpainRISE Research Institutes of Sweden, 501 15 Borås, SwedenInstituto de Tecnología Eléctrica, Universitat Politècnica de València, Camino de Vera s/n, 46022 Valencia, SpainDepartment of Electrical Engineering, Tampere University (TAU), Korkeakoulunkatu 3, 33720 Tampere, FinlandFundación para el Fomento de la Innovación Industrial, FFII-LCOE, Eric Kandel Street 1, Getafe, 28906 Madrid, SpainDepartment of Electrical and Electronic Engineering, Automatic Control and Applied Physics, School of Industrial Design and Engineering (ETSIDI), Universidad Politécnica de Madrid (UPM), Ronda de Valencia 3, 28012 Madrid, SpainFundación para el Fomento de la Innovación Industrial, FFII-LCOE, Eric Kandel Street 1, Getafe, 28906 Madrid, SpainDepartment of Electrical and Electronic Engineering, Automatic Control and Applied Physics, School of Industrial Design and Engineering (ETSIDI), Universidad Politécnica de Madrid (UPM), Ronda de Valencia 3, 28012 Madrid, SpainRISE Research Institutes of Sweden, 501 15 Borås, SwedenOn-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270.https://www.mdpi.com/1424-8220/23/14/6317partial dischargescable insulationGIScondition monitoringinsulation testingqualification procedure |
spellingShingle | Fernando Garnacho Fernando Álvarez Alf-Peter Elg Christian Mier Kari Lahti Abderrahim Khamlichi Eduardo Arcones Joni Klüss Armando Rodrigo Mor Pertti Pakonen José Ramón Vidal Álvaro Camuñas Jorge Rovira Carlos Vera Miran Haider Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids Sensors partial discharges cable insulation GIS condition monitoring insulation testing qualification procedure |
title | Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids |
title_full | Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids |
title_fullStr | Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids |
title_full_unstemmed | Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids |
title_short | Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids |
title_sort | metrological qualification of pd analysers for insulation diagnosis of hvdc and hvac grids |
topic | partial discharges cable insulation GIS condition monitoring insulation testing qualification procedure |
url | https://www.mdpi.com/1424-8220/23/14/6317 |
work_keys_str_mv | AT fernandogarnacho metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT fernandoalvarez metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT alfpeterelg metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT christianmier metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT karilahti metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT abderrahimkhamlichi metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT eduardoarcones metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT jonikluss metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT armandorodrigomor metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT perttipakonen metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT joseramonvidal metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT alvarocamunas metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT jorgerovira metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT carlosvera metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids AT miranhaider metrologicalqualificationofpdanalysersforinsulationdiagnosisofhvdcandhvacgrids |