A Novel Overcurrent Suppression Strategy during Reclosing Process of MMC-HVDC

A modular multilevel converter based high-voltage DC (MMC-HVDC) system has been the most promising topology for HVDC. A reclosing scheme is usually configured because temporary faults often occur on transmission lines especially when overhead lines are used, which often brings about an overcurrent p...

Full description

Bibliographic Details
Main Authors: Bin Jiang, Yanfeng Gong
Format: Article
Language:English
Published: MDPI AG 2019-04-01
Series:Applied Sciences
Subjects:
Online Access:https://www.mdpi.com/2076-3417/9/9/1737
Description
Summary:A modular multilevel converter based high-voltage DC (MMC-HVDC) system has been the most promising topology for HVDC. A reclosing scheme is usually configured because temporary faults often occur on transmission lines especially when overhead lines are used, which often brings about an overcurrent problem. In this paper, a new fault current limiter (FCL) based on reclosing current limiting resistance (RCLR) is proposed to solve the overcurrent problem during the reclosing process. Firstly, a mesh current method (MCM) based short-circuit current calculation method is newly proposed to solve the fault current calculation of a loop MMC-HVDC grid. Then the method to calculate the RCLR is proposed based on the arm current to limit the arm currents to a specified value during the reclosing process. Finally, a three-terminal loop MMC-HVDC test grid is constructed in the widely used electromagnetic transient simulation software PSCAD/EMTDC and the simulations prove the effectiveness of the proposed strategy.
ISSN:2076-3417