Investigation and Control of Damping in VSC–MTDC System with DC Circuit Breakers

DC circuit breaker (DCCB) systems with a DC reactor in series are normally equipped in the voltage-sourced-converter-based multi-terminal DC (VSC–MTDC) systems for DC fault clearance. However, it is revealed that the use of DC reactors could undermine the system damping and deteriorate the system st...

Full description

Bibliographic Details
Main Authors: Wenzhong Ma, Jianyi Gao, Guanyu Zhou, Yan Zhang, Kuitong Zhang, Jia Han, Lei Dong
Format: Article
Language:English
Published: MDPI AG 2021-10-01
Series:Symmetry
Subjects:
Online Access:https://www.mdpi.com/2073-8994/13/11/2037
Description
Summary:DC circuit breaker (DCCB) systems with a DC reactor in series are normally equipped in the voltage-sourced-converter-based multi-terminal DC (VSC–MTDC) systems for DC fault clearance. However, it is revealed that the use of DC reactors could undermine the system damping and deteriorate the system stability. In this paper, a controller based on hybrid sensitivity is proposed to improve the stability of power system and realize the power symmetry of multi-terminal systems. Firstly, based on a generalized MTDC small-signal model, an eigenvalue analysis is performed to provide deep insight into the stability issue imposed by DC reactors. Furthermore, a local controller based on hybrid sensitivity was proposed, and on this basis, a global controller was designed to solve asymmetrical power flow. Finally, a four-terminal VSC–MTDC model was built in Simulink to evaluate the performance of DC-PSS. Simulation results verify the effectiveness of the proposed controller in stabilizing MTDC systems and symmetrizing of power flow.
ISSN:2073-8994