Summary: | The model is proposed for the calculation and research of steady state asymmetric modes and transients in three-phase three legs transformer devices with arbitrary diagram of windings connection, taking into account the electromagnetic coupling of the windings, located on different legs. Using as an example distribution transformer of 10/0.4 kV calculations and analysis were performed of the most characteristic steady asymmetrical modes, that occur during short circuit, phase failure, unbalanced load for the most common windings connections and, in particular, associated with the occurrence of zero sequence magnetic flow. For the considered regimes and schemes vector diagrams were constructed for currents and voltages as well as for the relative values of magnetic flow, which give a clear idea about their particular features.
|