Summary: | This paper presents the electrical system factors having an influence on the work efficiency and performance of the <i>LC</i> passive harmonic filters (PHFs). Such filters are very often used in industries for the purpose of harmonics mitigation and reactive power compensation. Before their installation in the electrical system, many investigations should be performed in order to ensure their good design as well as work efficiency after connection. In this paper, the factors having an influence on the PHFs work efficiency and performance, such as the grid short-circuit power, primary grid voltage spectrum (voltage measured at the PCC before the filter connection), load reactive power and current characteristic harmonics, manufacturer filter parameters tolerance and filter-detuning phenomena are investigated. Most of the quoted factors are mentioned in the literature, but the novelty of this paper is that, based on the case study example of the single-tuned filter investigated in the laboratory, the influence of those factors on the filter work efficiency are demonstrated, and some solutions and recommendations are proposed. The studies are focused on the design of the single-tuned filter in the laboratory, and some simulation results are presented as well.
|