Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions

Data-driven Automated Fault Detection and Diagnosis (AFDD) are recognized as one of the most promising options to improve the efficiency of Air-Handling Units (AHUs). In this study, the field operation of a typical single-duct dual-fan constant air volume AHU is investigated through a series of expe...

Full description

Bibliographic Details
Main Authors: Antonio Rosato, Francesco Guarino, Mohammad El Youssef, Alfonso Capozzoli, Massimiliano Masullo, Luigi Maffei
Format: Article
Language:English
Published: MDPI AG 2022-09-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/15/18/6781
_version_ 1797488758123134976
author Antonio Rosato
Francesco Guarino
Mohammad El Youssef
Alfonso Capozzoli
Massimiliano Masullo
Luigi Maffei
author_facet Antonio Rosato
Francesco Guarino
Mohammad El Youssef
Alfonso Capozzoli
Massimiliano Masullo
Luigi Maffei
author_sort Antonio Rosato
collection DOAJ
description Data-driven Automated Fault Detection and Diagnosis (AFDD) are recognized as one of the most promising options to improve the efficiency of Air-Handling Units (AHUs). In this study, the field operation of a typical single-duct dual-fan constant air volume AHU is investigated through a series of experiments carried out under Mediterranean (southern Italy) climatic conditions considering both fault-free and faulty scenarios. The AHU performances are analyzed while artificially introducing the following five different typical faults: (1) post-heating coil valve stuck at 100% (always open); (2) post-heating coil valve stuck at 0% (always closed); (3) cooling coil valve stuck at 100% (always open); (4) cooling coil valve stuck at 0% (always closed); (5) humidifier valve stuck at 0% (always closed). The measured faulty data are compared against the corresponding fault-free performance measured under the same boundary conditions with the aim of assessing the faults’ impact on both thermal/hygrometric indoor conditions, as well as patterns of 16 different key operating parameters. The results of this study can help building operators and facility engineers in identifying faults’ symptoms in typical AHUs and facilitate the related development of new AFDD tools.
first_indexed 2024-03-10T00:06:52Z
format Article
id doaj.art-108079ae6a914351aa0a2d328fe3e605
institution Directory Open Access Journal
issn 1996-1073
language English
last_indexed 2024-03-10T00:06:52Z
publishDate 2022-09-01
publisher MDPI AG
record_format Article
series Energies
spelling doaj.art-108079ae6a914351aa0a2d328fe3e6052023-11-23T16:05:41ZengMDPI AGEnergies1996-10732022-09-011518678110.3390/en15186781Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic ConditionsAntonio Rosato0Francesco Guarino1Mohammad El Youssef2Alfonso Capozzoli3Massimiliano Masullo4Luigi Maffei5Department of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyDepartment of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, Via San Lorenzo 4, 81031 Aversa, ItalyData-driven Automated Fault Detection and Diagnosis (AFDD) are recognized as one of the most promising options to improve the efficiency of Air-Handling Units (AHUs). In this study, the field operation of a typical single-duct dual-fan constant air volume AHU is investigated through a series of experiments carried out under Mediterranean (southern Italy) climatic conditions considering both fault-free and faulty scenarios. The AHU performances are analyzed while artificially introducing the following five different typical faults: (1) post-heating coil valve stuck at 100% (always open); (2) post-heating coil valve stuck at 0% (always closed); (3) cooling coil valve stuck at 100% (always open); (4) cooling coil valve stuck at 0% (always closed); (5) humidifier valve stuck at 0% (always closed). The measured faulty data are compared against the corresponding fault-free performance measured under the same boundary conditions with the aim of assessing the faults’ impact on both thermal/hygrometric indoor conditions, as well as patterns of 16 different key operating parameters. The results of this study can help building operators and facility engineers in identifying faults’ symptoms in typical AHUs and facilitate the related development of new AFDD tools.https://www.mdpi.com/1996-1073/15/18/6781heating, ventilation and air-conditioning systemsair-handling unitheating coil valve stuckcooling coil valve stuckhumidifier valve stuckfaulty experimental data
spellingShingle Antonio Rosato
Francesco Guarino
Mohammad El Youssef
Alfonso Capozzoli
Massimiliano Masullo
Luigi Maffei
Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
Energies
heating, ventilation and air-conditioning systems
air-handling unit
heating coil valve stuck
cooling coil valve stuck
humidifier valve stuck
faulty experimental data
title Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
title_full Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
title_fullStr Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
title_full_unstemmed Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
title_short Faulty Operation of Coils’ and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions
title_sort faulty operation of coils and humidifier valves in a typical air handling unit experimental impact assessment of indoor comfort and patterns of operating parameters under mediterranean climatic conditions
topic heating, ventilation and air-conditioning systems
air-handling unit
heating coil valve stuck
cooling coil valve stuck
humidifier valve stuck
faulty experimental data
url https://www.mdpi.com/1996-1073/15/18/6781
work_keys_str_mv AT antoniorosato faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions
AT francescoguarino faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions
AT mohammadelyoussef faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions
AT alfonsocapozzoli faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions
AT massimilianomasullo faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions
AT luigimaffei faultyoperationofcoilsandhumidifiervalvesinatypicalairhandlingunitexperimentalimpactassessmentofindoorcomfortandpatternsofoperatingparametersundermediterraneanclimaticconditions