Fire behaviour of steel members penetrating concrete walls
In steel construction, it is often desirable for a steel member to pass through a concrete fire wall rather than being curtailed at the wall. In situations where a steel member penetrates a fire wall, the member will usually be fire protected for a certain length on each side of the wall so as to m...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
Electronic Journals for Science and Engineering - International
2001-01-01
|
Series: | Electronic Journal of Structural Engineering |
Subjects: | |
Online Access: | http://10.0.0.97/EJSE/article/view/13 |
Summary: | In steel construction, it is often desirable for a steel member to pass through a concrete fire wall rather than being curtailed at the wall. In situations where a steel member penetrates a fire wall, the member will usually be fire protected for a certain length on each side of the wall so as to minimise the heat flow through the steel member and reduce the likelihood of ignition of combustibles on the non-fire (unexposed) side within the adjacent compartment. The testing reported in this paper suggests that it is not necessary to apply fire protection to each side of a penetrating steel member since the resulting temperature rise of the member is insufficient to cause ignition.
|
---|---|
ISSN: | 1443-9255 |