ACCEPTABLE LIMITS FOR CORRECTION OF HEATING LOAD WHILE OPTIMIZING OPERATIONAL MODES OF HEAT SOURCES

Numerical investigations of temperature fields in the apartments of a multi-dwelling building has been carried out on the basis of the developed mathematical model and algorithm of its realization. The investigations have  made it possible to evaluate dynamics of changes in air temperature under uns...

Full description

Bibliographic Details
Main Authors: P. I. Diachek, V. A. Sednin, A. E. Zakharevich, I. V. Shkliar
Format: Article
Language:Russian
Published: Belarusian National Technical University 2014-02-01
Series:Izvestiâ Vysših Učebnyh Zavedenij i Ènergetičeskih ob Edinennij SNG. Ènergetika
Subjects:
Online Access:https://energy.bntu.by/jour/article/view/763
Description
Summary:Numerical investigations of temperature fields in the apartments of a multi-dwelling building has been carried out on the basis of the developed mathematical model and algorithm of its realization. The investigations have  made it possible to evaluate dynamics of changes in air temperature under unsteady conditions due to increase or reduction heating device capacity with regard to standardized values. The calculation results have demonstrated that a permissible period for capacity change accounts for not more than 6 hours. At the same time the rate of capacity change is up to 40 %. The obtained results can be practically used in the intelligent heating supply systems with the purpose to minimize consumption of fuel and power resources