Fault section positioning and ranging method of distribution network

In view of problem that it is difficult to realize fault positioning by use of artificial patrol after single-phase grounding fault occurred in distribution network, a fault section positioning and ranging method of distribution network based on distributed parameter model was proposed. In the metho...

Full description

Bibliographic Details
Main Authors: GENG Xingwang, LUO Yanfang
Format: Article
Language:zho
Published: Editorial Department of Industry and Mine Automation 2015-01-01
Series:Gong-kuang zidonghua
Subjects:
Online Access:http://www.gkzdh.cn/article/doi/10.13272/j.issn.1671-251x.2015.01.022
Description
Summary:In view of problem that it is difficult to realize fault positioning by use of artificial patrol after single-phase grounding fault occurred in distribution network, a fault section positioning and ranging method of distribution network based on distributed parameter model was proposed. In the method, fault section is chosen through analyzing and calculating of fault information and date uploaded by feeder terminal unit of line, and fault distance is obtained by online calculating distributed parameters of the section line. The simulation results show that the method is less affected by factors of transition resistance and fault location, which can effectively realize fault line selection and section positioning within 1% ranging error.
ISSN:1671-251X