Parametric analysis of chiller plant energy consumption in a tropical climate

Abstract The approach that could reduce the energy consumption of water-cooled chillers in office buildings was investigated through experimental and simulation methods. The chiller was modelled in TRNSYS and validated using physical measurements from an operational water-cooled water chiller and fa...

Full description

Bibliographic Details
Main Authors: Esther Benedicta Kyere, Jen Tien-Chien, Lagouge Tartibu
Format: Article
Language:English
Published: Springer 2023-12-01
Series:International Journal of Air-Conditioning and Refrigeration
Subjects:
Online Access:https://doi.org/10.1007/s44189-023-00045-5
_version_ 1827581537518878720
author Esther Benedicta Kyere
Jen Tien-Chien
Lagouge Tartibu
author_facet Esther Benedicta Kyere
Jen Tien-Chien
Lagouge Tartibu
author_sort Esther Benedicta Kyere
collection DOAJ
description Abstract The approach that could reduce the energy consumption of water-cooled chillers in office buildings was investigated through experimental and simulation methods. The chiller was modelled in TRNSYS and validated using physical measurements from an operational water-cooled water chiller and fan coil system. The validated model was used to analyse the energy consumption of the water chiller-fan coil system under a high chilled water temperature setpoint (CWTS) in a representative commercial office building. Subsequently, indoor thermal comfort was evaluated using the PMV-PPD model. Finally, the design of experiment (DOE) was employed using a statistical two-level non-randomized factorial design in Minitab to study the effects of high CWTS, number of rows, and tube diameter on the heat and mass transfer performance of the fan coil unit. The results showed that the CWTS can be increased by various degrees from 10 up to 18 °C for energy efficiency for a commercial office building in the tropics. This increase in CWTS would result in a daily energy saving potential of about 5% of the chiller as compared to the existing operational settings without any extra cost. Conversely, the daily energy consumption by the fan coil would increase by about 5.5% by this increment in the CWTS. It was determined that the chiller system can provide comfort even when the CWTS is increased to 14 °C. The DOE analysis showed that under the condition of high CWTS (14 °C), energy consumption that is less than the current energy consumption may be expected from the fan coil system when the number of rows increased from 3 to 6 and the tube diameter increased from 7 to 9 mm.
first_indexed 2024-03-08T22:37:16Z
format Article
id doaj.art-52574af055344375984e727153035025
institution Directory Open Access Journal
issn 2010-1333
language English
last_indexed 2024-03-08T22:37:16Z
publishDate 2023-12-01
publisher Springer
record_format Article
series International Journal of Air-Conditioning and Refrigeration
spelling doaj.art-52574af055344375984e7271530350252023-12-17T12:21:28ZengSpringerInternational Journal of Air-Conditioning and Refrigeration2010-13332023-12-0131112210.1007/s44189-023-00045-5Parametric analysis of chiller plant energy consumption in a tropical climateEsther Benedicta Kyere0Jen Tien-Chien1Lagouge Tartibu2Mechanical Engineering Science, University of JohannesburgMechanical Engineering Science, University of JohannesburgMechanical and Industrial Engineering Technology, University of JohannesburgAbstract The approach that could reduce the energy consumption of water-cooled chillers in office buildings was investigated through experimental and simulation methods. The chiller was modelled in TRNSYS and validated using physical measurements from an operational water-cooled water chiller and fan coil system. The validated model was used to analyse the energy consumption of the water chiller-fan coil system under a high chilled water temperature setpoint (CWTS) in a representative commercial office building. Subsequently, indoor thermal comfort was evaluated using the PMV-PPD model. Finally, the design of experiment (DOE) was employed using a statistical two-level non-randomized factorial design in Minitab to study the effects of high CWTS, number of rows, and tube diameter on the heat and mass transfer performance of the fan coil unit. The results showed that the CWTS can be increased by various degrees from 10 up to 18 °C for energy efficiency for a commercial office building in the tropics. This increase in CWTS would result in a daily energy saving potential of about 5% of the chiller as compared to the existing operational settings without any extra cost. Conversely, the daily energy consumption by the fan coil would increase by about 5.5% by this increment in the CWTS. It was determined that the chiller system can provide comfort even when the CWTS is increased to 14 °C. The DOE analysis showed that under the condition of high CWTS (14 °C), energy consumption that is less than the current energy consumption may be expected from the fan coil system when the number of rows increased from 3 to 6 and the tube diameter increased from 7 to 9 mm.https://doi.org/10.1007/s44189-023-00045-5Chilled water temperature setpointFan coil systemEnergy savingPMV-PPDDOETRNSYS simulation
spellingShingle Esther Benedicta Kyere
Jen Tien-Chien
Lagouge Tartibu
Parametric analysis of chiller plant energy consumption in a tropical climate
International Journal of Air-Conditioning and Refrigeration
Chilled water temperature setpoint
Fan coil system
Energy saving
PMV-PPD
DOE
TRNSYS simulation
title Parametric analysis of chiller plant energy consumption in a tropical climate
title_full Parametric analysis of chiller plant energy consumption in a tropical climate
title_fullStr Parametric analysis of chiller plant energy consumption in a tropical climate
title_full_unstemmed Parametric analysis of chiller plant energy consumption in a tropical climate
title_short Parametric analysis of chiller plant energy consumption in a tropical climate
title_sort parametric analysis of chiller plant energy consumption in a tropical climate
topic Chilled water temperature setpoint
Fan coil system
Energy saving
PMV-PPD
DOE
TRNSYS simulation
url https://doi.org/10.1007/s44189-023-00045-5
work_keys_str_mv AT estherbenedictakyere parametricanalysisofchillerplantenergyconsumptioninatropicalclimate
AT jentienchien parametricanalysisofchillerplantenergyconsumptioninatropicalclimate
AT lagougetartibu parametricanalysisofchillerplantenergyconsumptioninatropicalclimate