Grounding System Modeling and Evaluation Using Integrated Circuit Based Fast Relaxed Vector Fitting Approach, Considering Soil Ionization

Since high voltage transmission line towers or wind turbines structures are installed in high-altitude areas, it is essential to achieve a high overvoltage protection system against direct and indirect lightning strikes collisions. The lightning current must be discharged quickly into the protective...

Full description

Bibliographic Details
Main Authors: Maziyar Fakhraei, Mehrdad Mahmoudian, Eduardo Manuel Godinho Rodrigues
Format: Article
Language:English
Published: MDPI AG 2020-08-01
Series:Applied Sciences
Subjects:
Online Access:https://www.mdpi.com/2076-3417/10/16/5632
Description
Summary:Since high voltage transmission line towers or wind turbines structures are installed in high-altitude areas, it is essential to achieve a high overvoltage protection system against direct and indirect lightning strikes collisions. The lightning current must be discharged quickly into the protective earth, to prevent the dangerous over-voltages formation and define a reference voltage node. This paper presents a novel model to assess the behavior of the grounding system, based on Pocklington integral equations under lightning magnetic fields and variations in soil ionization, in which an explicit circuit-based vector fitting RLC admittance branches are proposed. The frequency-dependent behavior of grounding system frequency response and soil ionization effect is modeled in time domain, straightly to implement into the electro-magnetic transient program (EMTP). The model verification contains horizontal, vertical, and their combinations of grounding grids to represent the complete investigations under lightning strikes. The harmonic impedance mathematical formulations and principles are derived based on a rational function, that could be applicable on ground potential rise (GPR) investigation.
ISSN:2076-3417