Computation method for analysis of sliding faults in power systems

Short-circuit analysis is conducted based on the nodal impedance matrix, which is the inversion of the nodal admittance matrix. If analysis is conducted for sliding faults, then for each fault location four elements of the nodal admittance matrix are subject to changes and the calculation of the adm...

Full description

Bibliographic Details
Main Authors: Jan Machowski, Sylwester Robak
Format: Article
Language:English
Published: Polish Academy of Sciences 2021-01-01
Series:Bulletin of the Polish Academy of Sciences: Technical Sciences
Subjects:
Online Access:https://journals.pan.pl/Content/118763/PDF/08_01933_Bpast.No.69(1)_27.01.21_K2_A.pdf
Description
Summary:Short-circuit analysis is conducted based on the nodal impedance matrix, which is the inversion of the nodal admittance matrix. If analysis is conducted for sliding faults, then for each fault location four elements of the nodal admittance matrix are subject to changes and the calculation of the admittance matrix inversion needs to be repeated many times. For large-scale networks such an approach is time consuming and unsatisfactory. This paper proves that for each new fault location a new impedance matrix can be found without recalculation of the matrix inversion. It can be found by a simple extension of the initial nodal impedance matrix calculated once for the input model of the network. This paper derives formulas suitable for such an extension and presents a flowchart of the computational method. Numerical tests performed for a test power system confirm the validity and usefulness of the proposed method.
ISSN:2300-1917