Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature
Solar-driven ammonia-water absorption refrigeration system (AARS) has been considered as an alternative for the conventional refrigeration and air-conditioning systems. However, its high initial cost seems to be the main problem that postpones its wide spread use. In the present study, a single-stag...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
MDPI AG
2017-10-01
|
Series: | Energies |
Subjects: | |
Online Access: | https://www.mdpi.com/1996-1073/10/11/1746 |
_version_ | 1798004040147140608 |
---|---|
author | Osman Wageiallah Mohammed Guo Yanling |
author_facet | Osman Wageiallah Mohammed Guo Yanling |
author_sort | Osman Wageiallah Mohammed |
collection | DOAJ |
description | Solar-driven ammonia-water absorption refrigeration system (AARS) has been considered as an alternative for the conventional refrigeration and air-conditioning systems. However, its high initial cost seems to be the main problem that postpones its wide spread use. In the present study, a single-stage NH3/H2O ARS is analyzed in depth on the basis of energetic and exergetic coefficients of performance (COP and ECOP, respectively) to decrease its cut in/off temperature. This study was carried out to lower the required heat source temperature, so that a less-expensive solar collector could be used. Effects of all parameters that could influence the system’s performance and cut in/off temperature were investigated in detail. Presence of water in the refrigerant and evaporator temperature glide was considered. Results revealed that appropriate selection of system’s working condition can effectively reduce the driving temperature. Besides, the cut in/off temperature can be significantly decreased by inserting an effective solution heat exchanger (SHX). Required driving temperature can be lowered by up to 10 °C using SHX with 0.80 effectiveness. The results also showed that effects of water content in the refrigerant could not be neglected in studying NH3/H2O ARS because it affects both COP and ECOP. Additionally, a large temperature glide in the evaporator can substantially decrease the ECOP. |
first_indexed | 2024-04-11T12:17:07Z |
format | Article |
id | doaj.art-7f07b0eedc8a44a79bdf9bc99af02786 |
institution | Directory Open Access Journal |
issn | 1996-1073 |
language | English |
last_indexed | 2024-04-11T12:17:07Z |
publishDate | 2017-10-01 |
publisher | MDPI AG |
record_format | Article |
series | Energies |
spelling | doaj.art-7f07b0eedc8a44a79bdf9bc99af027862022-12-22T04:24:15ZengMDPI AGEnergies1996-10732017-10-011011174610.3390/en10111746en10111746Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off TemperatureOsman Wageiallah Mohammed0Guo Yanling1College of Mechanical and Electrical Engineering, Northeast Forestry University, Harbin 150000, ChinaCollege of Mechanical and Electrical Engineering, Northeast Forestry University, Harbin 150000, ChinaSolar-driven ammonia-water absorption refrigeration system (AARS) has been considered as an alternative for the conventional refrigeration and air-conditioning systems. However, its high initial cost seems to be the main problem that postpones its wide spread use. In the present study, a single-stage NH3/H2O ARS is analyzed in depth on the basis of energetic and exergetic coefficients of performance (COP and ECOP, respectively) to decrease its cut in/off temperature. This study was carried out to lower the required heat source temperature, so that a less-expensive solar collector could be used. Effects of all parameters that could influence the system’s performance and cut in/off temperature were investigated in detail. Presence of water in the refrigerant and evaporator temperature glide was considered. Results revealed that appropriate selection of system’s working condition can effectively reduce the driving temperature. Besides, the cut in/off temperature can be significantly decreased by inserting an effective solution heat exchanger (SHX). Required driving temperature can be lowered by up to 10 °C using SHX with 0.80 effectiveness. The results also showed that effects of water content in the refrigerant could not be neglected in studying NH3/H2O ARS because it affects both COP and ECOP. Additionally, a large temperature glide in the evaporator can substantially decrease the ECOP.https://www.mdpi.com/1996-1073/10/11/1746solar assisted coolingheat pumpssolar thermal systemsabsorption refrigeration |
spellingShingle | Osman Wageiallah Mohammed Guo Yanling Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature Energies solar assisted cooling heat pumps solar thermal systems absorption refrigeration |
title | Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature |
title_full | Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature |
title_fullStr | Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature |
title_full_unstemmed | Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature |
title_short | Comprehensive Parametric Study of a Solar Absorption Refrigeration System to Lower Its Cut In/Off Temperature |
title_sort | comprehensive parametric study of a solar absorption refrigeration system to lower its cut in off temperature |
topic | solar assisted cooling heat pumps solar thermal systems absorption refrigeration |
url | https://www.mdpi.com/1996-1073/10/11/1746 |
work_keys_str_mv | AT osmanwageiallahmohammed comprehensiveparametricstudyofasolarabsorptionrefrigerationsystemtoloweritscutinofftemperature AT guoyanling comprehensiveparametricstudyofasolarabsorptionrefrigerationsystemtoloweritscutinofftemperature |