An Improved Method for Determining The Interface Height of Smoke Layer in A Tunnel Fire

Smoke layer interface height is an important parameter in fire safety science. In this paper, two methods are proposed on the basis of integral ratio method and the least squares method. a series of experiments were conducted in a 1:10 scale model tunnel for determining the smoke layer interface hei...

Full description

Bibliographic Details
Main Authors: Xiong Kang, Liu Fang, Weng Miaocheng
Format: Article
Language:English
Published: EDP Sciences 2022-01-01
Series:E3S Web of Conferences
Online Access:https://www.e3s-conferences.org/articles/e3sconf/pdf/2022/23/e3sconf_roomvent2022_02023.pdf
Description
Summary:Smoke layer interface height is an important parameter in fire safety science. In this paper, two methods are proposed on the basis of integral ratio method and the least squares method. a series of experiments were conducted in a 1:10 scale model tunnel for determining the smoke layer interface height in tunnel fire. The interface height of the smoke layer determined by the new methods have been compared with other existing approaches, including integral ratio method, least squares method, N-percentage rule. The comparison results show that the results of the least squares method based on the transition layer can be relatively reasonable and agree well with the visual observations for all experimental condition. In addition, the usage scenarios and considerations of the N-percentage rule were also discussed.
ISSN:2267-1242