The Performance Analysis of an Integrated CO<sub>2</sub> Refrigeration System with Multi-Ejectors Installed in a Supermarket

The field data from an integrated CO<sub>2</sub> refrigeration system installed in a supermarket located north of the capital of Lisbon was analyzed. The goal was to demonstrate the effect and performance of multi-ejectors on a refrigeration system operating in a warm climate. The measur...

Full description

Bibliographic Details
Main Authors: Engin Söylemez, Armin Hafner, Christian Schlemminger, Ekaterini E. Kriezi, Vahid Khorshidi
Format: Article
Language:English
Published: MDPI AG 2022-04-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/15/9/3142
Description
Summary:The field data from an integrated CO<sub>2</sub> refrigeration system installed in a supermarket located north of the capital of Lisbon was analyzed. The goal was to demonstrate the effect and performance of multi-ejectors on a refrigeration system operating in a warm climate. The measurement results for the system with and without activating ejectors were compared. It was observed that the system with a multi-ejector operation had considerable performance superiority. The ejectors improved the cooling capacity of the medium temperature stage of the system by 17.4%. The system with active ejectors had 7.5% less total power consumption compared to the ejector off mode of the same system.