Effect of change factors on evaporation loss based on cold end system in natural draft counter-flow wet cooling towers
The water loss caused by evaporation heat dissipation is non-negligible for a natural draft counter-flow wet cooling tower (NDWCT), which is evidently influenced by many change factors. Based on Merkel method, the Merkel number is revised in consideration of the effect of water loss. Taking the NDWC...
Main Authors: | Wei YUAN, Fengzhong SUN, Ruqing LIU, Xuehong CHEN, Ying LI |
---|---|
Format: | Article |
Language: | English |
Published: |
The Japan Society of Mechanical Engineers
2021-01-01
|
Series: | Journal of Thermal Science and Technology |
Subjects: | |
Online Access: | https://www.jstage.jst.go.jp/article/jtst/16/2/16_2021jtst0015/_pdf/-char/en |