Design of On-line Monitoring System for Temperature of Isolator Contacts of Mine-used High-voltage Distribution Equipment

For problems that high temperature caused by bad contact of isolator of mine-used high-voltage distribution equipment usually leads to faults and the faults are hardly detected, a design scheme of on-line monitoring system for temperature of isolator contact of mine-used high-voltage distribution eq...

Full description

Bibliographic Details
Main Authors: WU Jun-feng, SONG Jian-cheng, QU Bing-ni
Format: Article
Language:zho
Published: Editorial Department of Industry and Mine Automation 2011-09-01
Series:Gong-kuang zidonghua
Subjects:
Online Access:http://www.gkzdh.cn/article/id/5410
Description
Summary:For problems that high temperature caused by bad contact of isolator of mine-used high-voltage distribution equipment usually leads to faults and the faults are hardly detected, a design scheme of on-line monitoring system for temperature of isolator contact of mine-used high-voltage distribution equipment was put forward and software designs of lower computer program and on-line monitoring program based on LabVIEW of the system were introduced emphatically. The test result showed that the system can monitor temperature of isolator contact of mine-used high-voltage distribution equipment real-timely and remotely with error less than 1 ℃, which can meet requirement of actual project. Besides, the system has functions of fault diagnosis and early warning according to monitored temperature signal.