Indirect lightning performance of 10-kV overhead distribution lines

The lightning-induced voltage in 10-kV overhead distribution lines was calculated and analyzed using the Agrawal coupling model and second-order finite difference-time domain (FDTD) method. The influence of lightning position on lightning-induced voltage was analyzed using the concept of indirect li...

Full description

Bibliographic Details
Main Authors: Jianli Yu, Shanmao Gu, Jianjun Liu, He Liu
Format: Article
Language:English
Published: Frontiers Media S.A. 2024-03-01
Series:Frontiers in Energy Research
Subjects:
Online Access:https://www.frontiersin.org/articles/10.3389/fenrg.2024.1367183/full
Description
Summary:The lightning-induced voltage in 10-kV overhead distribution lines was calculated and analyzed using the Agrawal coupling model and second-order finite difference-time domain (FDTD) method. The influence of lightning position on lightning-induced voltage was analyzed using the concept of indirect lightning withstanding levels. To achieve the limiting effect on lightning-induced voltage in 10-kV lines, the installation density of surge arresters should not be less than 1 group per 200–300 m.
ISSN:2296-598X