Diagnostic System of Power Oil Transformer in Accordance with Thermal Parameters
The paper proposes a device and algorithms for early detection of slowly developing faults in a power transformer that cause its abnormal heating. The device differentiates from the others that it requires only temperature measurement of transformer tank surface and ambient temperatures. Experiment...
Main Authors: | , |
---|---|
Format: | Article |
Language: | Russian |
Published: |
Belarusian National Technical University
2013-10-01
|
Series: | Izvestiâ Vysših Učebnyh Zavedenij i Ènergetičeskih ob Edinennij SNG. Ènergetika |
Online Access: | https://energy.bntu.by/jour/article/view/125 |
Summary: | The paper proposes a device and algorithms for early detection of slowly developing faults in a power transformer that cause its abnormal heating. The device differentiates from the others that it requires only temperature measurement of transformer tank surface and ambient temperatures. Experimental 63 MV×A autotransformer tests have proved faithfulness of the developed algorithms. |
---|---|
ISSN: | 1029-7448 2414-0341 |