The use of artificial neural network for low latency of fault detection and localisation in transmission line

One of the most critical concerns in power system reliability is the timely and accurate detection of transmission line faults. Therefore, accurate detection and localisation of these faults are necessary to avert system collapse. This paper focuses on using Artificial Neural Networks in faults dete...

Full description

Bibliographic Details
Main Authors: Vincent Nsed Ogar, Sajjad Hussain, Kelum A.A. Gamage
Format: Article
Language:English
Published: Elsevier 2023-02-01
Series:Heliyon
Subjects:
Online Access:http://www.sciencedirect.com/science/article/pii/S2405844023005832
Description
Summary:One of the most critical concerns in power system reliability is the timely and accurate detection of transmission line faults. Therefore, accurate detection and localisation of these faults are necessary to avert system collapse. This paper focuses on using Artificial Neural Networks in faults detection and localisation to attain accuracy, precision and speed of execution. A 330 kV, 500 km three-phase transmission line was modelled to extract faulty current and voltage data from the line. The Artificial Neural Network technique was used to train this data, and an accuracy of 100% was attained for fault detection and about 99.5% for fault localisation at different distances with 0.0017 μs of detection and an average error of 0%–0.5%. This model performs better than Support Vector Machine and Principal Component Analysis with a higher fault detection time. This proposed model serves as the basis for transmission line fault protection and management system.
ISSN:2405-8440