Account of Mechanical Characteristics of Generalized Drive in Algorithm of Fast-Acting Self-Start of High-Voltage Synchronous Motors

Object of the investigation is control systems of high-voltage synchronous motors which are applied at industrial enterprises with continuous technological process.A mathematical model for the run-out of generalized assembly including a motor and a mechanism has been developed. Analytical relations...

Full description

Bibliographic Details
Main Authors: V. V. Kourganau, U. V. Kryshneu, B. A. Vyaryga
Format: Article
Language:Russian
Published: Belarusian National Technical University 2007-04-01
Series:Izvestiâ Vysših Učebnyh Zavedenij i Ènergetičeskih ob Edinennij SNG. Ènergetika
Online Access:https://energy.bntu.by/jour/article/view/644
Description
Summary:Object of the investigation is control systems of high-voltage synchronous motors which are applied at industrial enterprises with continuous technological process.A mathematical model for the run-out of generalized assembly including a motor and a mechanism has been developed. Analytical relations between power failure time of electromotive load node and dynamic characteristics of high voltage synchronous motor run-out have been obtained. The method for fast acting synchronous motor self-start has been developed, that provides for determining an optimum time of tuming-on stand-by power for a group of electric motors, taking into account the measured value of an initial angular acceleration for a group run-out.