Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė

The operational eco-intensity of a heat supply system is dependent upon the interaction of its elements and their common performance. It is of special importance to gain insight into possibilities to reduce chip fuel consumption in the case when an additional element – a gas condenser – is installed...

Full description

Bibliographic Details
Main Authors: Dagnija Blumberga, Edgars Vīgants, Ivars Veidenbergs, Ģirts Vīgants, Valdis Vītoliņš
Format: Article
Language:English
Published: Vilnius Gediminas Technical University 2012-11-01
Series:Journal of Environmental Engineering and Landscape Management
Subjects:
Online Access:https://www.mla.vgtu.lt/index.php/JEELM/article/view/4644
_version_ 1818386828714049536
author Dagnija Blumberga
Edgars Vīgants
Ivars Veidenbergs
Ģirts Vīgants
Valdis Vītoliņš
author_facet Dagnija Blumberga
Edgars Vīgants
Ivars Veidenbergs
Ģirts Vīgants
Valdis Vītoliņš
author_sort Dagnija Blumberga
collection DOAJ
description The operational eco-intensity of a heat supply system is dependent upon the interaction of its elements and their common performance. It is of special importance to gain insight into possibilities to reduce chip fuel consumption in the case when an additional element – a gas condenser – is installed in a boiler house. The efficiency of a system's operation is estimated by its eco-intensity; such estimates concern the influence exerted by technological parameters on the reduction in natural resource consumption, allowing this problem to be thoroughly analysed by means of definite factors promoting the eco-intensity rise. Based on the results of commercial experiment, the authors have found the independent variables for the case of gas condenser without packing. The eco-intensity of a boiler house operation decreases as the outdoor temperature falls and therefore the boiler's load should be increased. This aspect could be due to several causes, among which the most important are: the deviations of the operating parameters of the gas condenser, the increase in the flue gas velocity, and temperature. Analytical treatment of the influence exerted by a boiler's specific load on the operational efficiency of its energy has shown that as this former grows, the efficiency decreases and therefore less heat energy could be derived from the gas condenser. This should be taken into account at simulation of the control over a gas condenser's operation. Santrauka Ekologinis intensyvumas priklauso nuo šilumos tiekimo sistemos elementų sąveikos ir jų bendro veikimo. Tai ypač svarbu tiriant galimybes sumažinti skiedrų kuro sąnaudas tuo atveju, kai šildomame name yra įdiegtas papildomas elementas – dujų kondensatorius. Sistemos veikimo efektyvumas įvertinamas pagal jos ekologinį intensyvumą; tokie vertinimai susiję su įtaka technologiniams parametrams mažinant gamtinių išteklių naudojimą. Remdamiesi tyrimo duomenimis, autoriai nustatė nepriklausomuosius dujų kondensatoriaus kintamuosius. Šildomo namo ekologinis intensyvumas susijęs su lauko temperatūra. Kai ji nukrinta, apkrova turėtų būti padidinama. Tai lemia kelios priežastys, iš jų svarbiausios: dujų kondensatoriaus darbinių parametrų nuokrypiai, išmetamųjų dujų greičio padidėjimas ir temperatūra. Atlikta analizė parodė, kad didinant katilo formą, sistemos efektyvumas mažėja, ir todėl mažiau šilumos energijos tiekiama iš dujų kondensatoriaus. Tai turėtų būti įtraukta į dujų kondensatoriaus veikimo kontrolės modeliavimo skaičiavimus. Reikšminiai žodžiai: dujų kondensatorius, skiedromis šildomas namas, šilumos tiekimo sistema, optimizacija, ekologinis intensyvumas, komerciniai tyrimai, aplinkos tausojimas
first_indexed 2024-12-14T04:00:15Z
format Article
id doaj.art-eecba0e22e08424bac448ebb5b4959b8
institution Directory Open Access Journal
issn 1648-6897
1822-4199
language English
last_indexed 2024-12-14T04:00:15Z
publishDate 2012-11-01
publisher Vilnius Gediminas Technical University
record_format Article
series Journal of Environmental Engineering and Landscape Management
spelling doaj.art-eecba0e22e08424bac448ebb5b4959b82022-12-21T23:17:58ZengVilnius Gediminas Technical UniversityJournal of Environmental Engineering and Landscape Management1648-68971822-41992012-11-0120410.3846/16486897.2012.695737Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizėDagnija Blumberga0Edgars Vīgants1Ivars Veidenbergs2Ģirts Vīgants3Valdis Vītoliņš4Riga Technical University, Institute of Energy Systems and Environment, Kronvalda blvd. 1, LV-1010 Riga, LatviaRiga Technical University, Institute of Energy Systems and Environment, Kronvalda blvd. 1, LV-1010 Riga, LatviaRiga Technical University, Institute of Energy Systems and Environment, Kronvalda blvd. 1, LV-1010 Riga, LatviaRiga Technical University, Institute of Energy Systems and Environment, Kronvalda blvd. 1, LV-1010 Riga, LatviaRiga Technical University, Institute of Energy Systems and Environment, Kronvalda blvd. 1, LV-1010 Riga, LatviaThe operational eco-intensity of a heat supply system is dependent upon the interaction of its elements and their common performance. It is of special importance to gain insight into possibilities to reduce chip fuel consumption in the case when an additional element – a gas condenser – is installed in a boiler house. The efficiency of a system's operation is estimated by its eco-intensity; such estimates concern the influence exerted by technological parameters on the reduction in natural resource consumption, allowing this problem to be thoroughly analysed by means of definite factors promoting the eco-intensity rise. Based on the results of commercial experiment, the authors have found the independent variables for the case of gas condenser without packing. The eco-intensity of a boiler house operation decreases as the outdoor temperature falls and therefore the boiler's load should be increased. This aspect could be due to several causes, among which the most important are: the deviations of the operating parameters of the gas condenser, the increase in the flue gas velocity, and temperature. Analytical treatment of the influence exerted by a boiler's specific load on the operational efficiency of its energy has shown that as this former grows, the efficiency decreases and therefore less heat energy could be derived from the gas condenser. This should be taken into account at simulation of the control over a gas condenser's operation. Santrauka Ekologinis intensyvumas priklauso nuo šilumos tiekimo sistemos elementų sąveikos ir jų bendro veikimo. Tai ypač svarbu tiriant galimybes sumažinti skiedrų kuro sąnaudas tuo atveju, kai šildomame name yra įdiegtas papildomas elementas – dujų kondensatorius. Sistemos veikimo efektyvumas įvertinamas pagal jos ekologinį intensyvumą; tokie vertinimai susiję su įtaka technologiniams parametrams mažinant gamtinių išteklių naudojimą. Remdamiesi tyrimo duomenimis, autoriai nustatė nepriklausomuosius dujų kondensatoriaus kintamuosius. Šildomo namo ekologinis intensyvumas susijęs su lauko temperatūra. Kai ji nukrinta, apkrova turėtų būti padidinama. Tai lemia kelios priežastys, iš jų svarbiausios: dujų kondensatoriaus darbinių parametrų nuokrypiai, išmetamųjų dujų greičio padidėjimas ir temperatūra. Atlikta analizė parodė, kad didinant katilo formą, sistemos efektyvumas mažėja, ir todėl mažiau šilumos energijos tiekiama iš dujų kondensatoriaus. Tai turėtų būti įtraukta į dujų kondensatoriaus veikimo kontrolės modeliavimo skaičiavimus. Reikšminiai žodžiai: dujų kondensatorius, skiedromis šildomas namas, šilumos tiekimo sistema, optimizacija, ekologinis intensyvumas, komerciniai tyrimai, aplinkos tausojimashttps://www.mla.vgtu.lt/index.php/JEELM/article/view/4644Gas condenserenergy efficiency improvementchip fuelled boiler househeat supply systemoptimizationeco-intensity
spellingShingle Dagnija Blumberga
Edgars Vīgants
Ivars Veidenbergs
Ģirts Vīgants
Valdis Vītoliņš
Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
Journal of Environmental Engineering and Landscape Management
Gas condenser
energy efficiency improvement
chip fuelled boiler house
heat supply system
optimization
eco-intensity
title Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
title_full Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
title_fullStr Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
title_full_unstemmed Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
title_short Eco-intensity analysis for a chip-fuelled boiler house / Ekologinio intesyvumo namą šildant skiedromis analizė
title_sort eco intensity analysis for a chip fuelled boiler house ekologinio intesyvumo nama sildant skiedromis analize
topic Gas condenser
energy efficiency improvement
chip fuelled boiler house
heat supply system
optimization
eco-intensity
url https://www.mla.vgtu.lt/index.php/JEELM/article/view/4644
work_keys_str_mv AT dagnijablumberga ecointensityanalysisforachipfuelledboilerhouseekologiniointesyvumonamasildantskiedromisanalize
AT edgarsvigants ecointensityanalysisforachipfuelledboilerhouseekologiniointesyvumonamasildantskiedromisanalize
AT ivarsveidenbergs ecointensityanalysisforachipfuelledboilerhouseekologiniointesyvumonamasildantskiedromisanalize
AT girtsvigants ecointensityanalysisforachipfuelledboilerhouseekologiniointesyvumonamasildantskiedromisanalize
AT valdisvitolins ecointensityanalysisforachipfuelledboilerhouseekologiniointesyvumonamasildantskiedromisanalize