Full-scale walk-in containerized lithium-ion battery energy storage system fire test data

Three installation-level lithium-ion battery (LIB) energy storage system (ESS) tests were conducted to the specifications of the UL 9540A standard test method [1]. Each test included a mocked-up initiating ESS unit rack and two target ESS unit racks installed within a standard size 6.06 m (20 ft) In...

Full description

Bibliographic Details
Main Authors: Mark McKinnon, Adam Barowy, Alexandra Schraiber, Jack Regan
Format: Article
Language:English
Published: Elsevier 2022-12-01
Series:Data in Brief
Subjects:
Online Access:http://www.sciencedirect.com/science/article/pii/S2352340922009167
_version_ 1811311008050839552
author Mark McKinnon
Adam Barowy
Alexandra Schraiber
Jack Regan
author_facet Mark McKinnon
Adam Barowy
Alexandra Schraiber
Jack Regan
author_sort Mark McKinnon
collection DOAJ
description Three installation-level lithium-ion battery (LIB) energy storage system (ESS) tests were conducted to the specifications of the UL 9540A standard test method [1]. Each test included a mocked-up initiating ESS unit rack and two target ESS unit racks installed within a standard size 6.06 m (20 ft) International Organization for Standardization (ISO) container. All tests were conducted with an identical LIB configuration. The initiating unit rack included nine modules (2,430 individual 18650 form factor cells) with a total capacity of 28.9 kWh. The target unit racks were loaded to one-third capacity of the initiating unit with nine partial modules and a total capacity of 9.6 kWh. All cells in the container were charged to 100% state-of-charge and none were electrically connected. Within the initiating mock-up unit, a flexible film heater was wrapped around an individual 18650 form factor cell. This instrumented 18650 cell was heated at a rate of 6°C/min to initiate thermal runaway.Test 1 was a baseline performance test and did not utilize any active fire suppression systems. Test 2 included a Novec 1230 system designed for an 8.3 vol% concentration discharged upon activation of two smoke detectors installed inside the container. Test 3 incorporated a dry pipe water suppression system to provide a uniform 20.8 mm/min (0.5 gpm/ft2) spray density delivered at the top of the ESS unit enclosures.Thermocouples were used to measure the cell temperatures in the initiating unit rack and module surface temperatures for the initiating unit and target unit racks. Thermocouples were located throughout the ISO container to measure gas temperatures and wall temperatures. Schmidt-Boelter heat flux gauges were installed to measure incident heat flux to each of the target unit racks as well as the walls adjacent to the initiating rack. Smoke detectors and smoke obscuration meters were used to identify the presence of smoke and characterize opacity of the smoke in the container. Various laboratory- and industrial-grade sensors were used to characterize the gas composition throughout container.
first_indexed 2024-04-13T10:10:17Z
format Article
id doaj.art-f3d06280f6c3439198f2bc83e6c0665a
institution Directory Open Access Journal
issn 2352-3409
language English
last_indexed 2024-04-13T10:10:17Z
publishDate 2022-12-01
publisher Elsevier
record_format Article
series Data in Brief
spelling doaj.art-f3d06280f6c3439198f2bc83e6c0665a2022-12-22T02:50:57ZengElsevierData in Brief2352-34092022-12-0145108712Full-scale walk-in containerized lithium-ion battery energy storage system fire test dataMark McKinnon0Adam Barowy1Alexandra Schraiber2Jack Regan3UL's Fire Safety Research Institute, 6200 Old Dobbin Ln. Ste. 150 Columbia, MD 21045, United StatesUL's Fire Safety Research Institute, 6200 Old Dobbin Ln. Ste. 150 Columbia, MD 21045, United States; UL Solutions Fire Research and Development, 333 Pfingsten Road, Northbrook, IL 60062, United States; Corresponding author at: UL's Fire Safety Research Institute, 6200 Old Dobbin Ln. Ste. 150 Columbia, MD 21045, United States.UL Solutions Fire Research and Development, 333 Pfingsten Road, Northbrook, IL 60062, United StatesUL's Fire Safety Research Institute, 6200 Old Dobbin Ln. Ste. 150 Columbia, MD 21045, United StatesThree installation-level lithium-ion battery (LIB) energy storage system (ESS) tests were conducted to the specifications of the UL 9540A standard test method [1]. Each test included a mocked-up initiating ESS unit rack and two target ESS unit racks installed within a standard size 6.06 m (20 ft) International Organization for Standardization (ISO) container. All tests were conducted with an identical LIB configuration. The initiating unit rack included nine modules (2,430 individual 18650 form factor cells) with a total capacity of 28.9 kWh. The target unit racks were loaded to one-third capacity of the initiating unit with nine partial modules and a total capacity of 9.6 kWh. All cells in the container were charged to 100% state-of-charge and none were electrically connected. Within the initiating mock-up unit, a flexible film heater was wrapped around an individual 18650 form factor cell. This instrumented 18650 cell was heated at a rate of 6°C/min to initiate thermal runaway.Test 1 was a baseline performance test and did not utilize any active fire suppression systems. Test 2 included a Novec 1230 system designed for an 8.3 vol% concentration discharged upon activation of two smoke detectors installed inside the container. Test 3 incorporated a dry pipe water suppression system to provide a uniform 20.8 mm/min (0.5 gpm/ft2) spray density delivered at the top of the ESS unit enclosures.Thermocouples were used to measure the cell temperatures in the initiating unit rack and module surface temperatures for the initiating unit and target unit racks. Thermocouples were located throughout the ISO container to measure gas temperatures and wall temperatures. Schmidt-Boelter heat flux gauges were installed to measure incident heat flux to each of the target unit racks as well as the walls adjacent to the initiating rack. Smoke detectors and smoke obscuration meters were used to identify the presence of smoke and characterize opacity of the smoke in the container. Various laboratory- and industrial-grade sensors were used to characterize the gas composition throughout container.http://www.sciencedirect.com/science/article/pii/S2352340922009167Lithium-IonThermal runawayEnergy storage systemFireSuppressionUL 9540A Test method
spellingShingle Mark McKinnon
Adam Barowy
Alexandra Schraiber
Jack Regan
Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
Data in Brief
Lithium-Ion
Thermal runaway
Energy storage system
Fire
Suppression
UL 9540A Test method
title Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
title_full Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
title_fullStr Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
title_full_unstemmed Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
title_short Full-scale walk-in containerized lithium-ion battery energy storage system fire test data
title_sort full scale walk in containerized lithium ion battery energy storage system fire test data
topic Lithium-Ion
Thermal runaway
Energy storage system
Fire
Suppression
UL 9540A Test method
url http://www.sciencedirect.com/science/article/pii/S2352340922009167
work_keys_str_mv AT markmckinnon fullscalewalkincontainerizedlithiumionbatteryenergystoragesystemfiretestdata
AT adambarowy fullscalewalkincontainerizedlithiumionbatteryenergystoragesystemfiretestdata
AT alexandraschraiber fullscalewalkincontainerizedlithiumionbatteryenergystoragesystemfiretestdata
AT jackregan fullscalewalkincontainerizedlithiumionbatteryenergystoragesystemfiretestdata