Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences

This study investigated to what extent the indoor environment with air-recirculating fan-coil units (FCU) could protect human from outdoor particles during hazy days. Different grade filters (25%, 65%, 85%, and 95%) were attached onto FCU in various rooms in order to get a result of best-performed f...

Full description

Bibliographic Details
Main Author: Xu, Xiaoqian
Other Authors: Chang Wei-Chung
Format: Final Year Project (FYP)
Language:English
Published: 2016
Subjects:
Online Access:http://hdl.handle.net/10356/68468
_version_ 1824456215203151872
author Xu, Xiaoqian
author2 Chang Wei-Chung
author_facet Chang Wei-Chung
Xu, Xiaoqian
author_sort Xu, Xiaoqian
collection NTU
description This study investigated to what extent the indoor environment with air-recirculating fan-coil units (FCU) could protect human from outdoor particles during hazy days. Different grade filters (25%, 65%, 85%, and 95%) were attached onto FCU in various rooms in order to get a result of best-performed filter. Every day of monitoring was divided into two periods, which are static period from 12AM to 7AM and active period, which is from 8:30AM to 6:30PM. Performances of filters were examined respect to the indoor-to-outdoor particles relationships, as well as the occupancy influences. We put our focus onto the particles within 2.5µm in diameter, since this phase of particles could penetrate human lungs to cause severe health problems. Data was collected through Optical Particle Counter (OPC) and Optical Particle Sizer (OPS) from 09/09/2015 to 25/09/2015. Particles were separated into 6 size channels (0.3-0.5µm, 0.5-1.0 µm, 1.0-2.5 µm, 2.5-5.0 µm, 5.0-10.0 µm, >10.0 µm), the first 3 channels represented PM2.5 value. Then PM2.5 data from NEA official website was recorded. Real-time particle volume concentrations (PVC) for first 3 channels were plotted against 24 hours on day 23/09/2015, which is a typically unhealthy level hazy day. ANOVA test was conducted for indoor-to-outdoor ratio (I/O ratio) of every two filters with successive removal efficiency grades so as to figure out if there is difference in its mean value. Overall efficiency was also calculated based on various parameters to quantify real removal efficiency. Occupancy level was recorded on hourly basis, indoor-to-outdoor (I/O) ratio for both of static period and active period were compared by paired sample t-test to check whether the mean values for accumulated PM2.5 (bin1 to bin3) differs by the occupancy. Hence, a filter application effect was also be quantified. Indoor particles movement could be affected by various parameters, such as airflow rate and air-recirculation rate of FCU, air exchange rate (AER) of the room as well as infiltration factor. The results showed that the FCU with filter of 85% and 95% removal efficiency giving out similar and overall best performance among all, which can effectively reduce particle concentrations in indoor environment to a healthy level (37.5µg/m3).
first_indexed 2025-02-19T03:50:33Z
format Final Year Project (FYP)
id ntu-10356/68468
institution Nanyang Technological University
language English
last_indexed 2025-02-19T03:50:33Z
publishDate 2016
record_format dspace
spelling ntu-10356/684682023-03-03T17:05:57Z Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences Xu, Xiaoqian Chang Wei-Chung School of Civil and Environmental Engineering DRNTU::Engineering This study investigated to what extent the indoor environment with air-recirculating fan-coil units (FCU) could protect human from outdoor particles during hazy days. Different grade filters (25%, 65%, 85%, and 95%) were attached onto FCU in various rooms in order to get a result of best-performed filter. Every day of monitoring was divided into two periods, which are static period from 12AM to 7AM and active period, which is from 8:30AM to 6:30PM. Performances of filters were examined respect to the indoor-to-outdoor particles relationships, as well as the occupancy influences. We put our focus onto the particles within 2.5µm in diameter, since this phase of particles could penetrate human lungs to cause severe health problems. Data was collected through Optical Particle Counter (OPC) and Optical Particle Sizer (OPS) from 09/09/2015 to 25/09/2015. Particles were separated into 6 size channels (0.3-0.5µm, 0.5-1.0 µm, 1.0-2.5 µm, 2.5-5.0 µm, 5.0-10.0 µm, >10.0 µm), the first 3 channels represented PM2.5 value. Then PM2.5 data from NEA official website was recorded. Real-time particle volume concentrations (PVC) for first 3 channels were plotted against 24 hours on day 23/09/2015, which is a typically unhealthy level hazy day. ANOVA test was conducted for indoor-to-outdoor ratio (I/O ratio) of every two filters with successive removal efficiency grades so as to figure out if there is difference in its mean value. Overall efficiency was also calculated based on various parameters to quantify real removal efficiency. Occupancy level was recorded on hourly basis, indoor-to-outdoor (I/O) ratio for both of static period and active period were compared by paired sample t-test to check whether the mean values for accumulated PM2.5 (bin1 to bin3) differs by the occupancy. Hence, a filter application effect was also be quantified. Indoor particles movement could be affected by various parameters, such as airflow rate and air-recirculation rate of FCU, air exchange rate (AER) of the room as well as infiltration factor. The results showed that the FCU with filter of 85% and 95% removal efficiency giving out similar and overall best performance among all, which can effectively reduce particle concentrations in indoor environment to a healthy level (37.5µg/m3). Bachelor of Engineering (Environmental Engineering) 2016-05-26T04:04:05Z 2016-05-26T04:04:05Z 2016 Final Year Project (FYP) http://hdl.handle.net/10356/68468 en Nanyang Technological University 43 p. application/pdf
spellingShingle DRNTU::Engineering
Xu, Xiaoqian
Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title_full Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title_fullStr Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title_full_unstemmed Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title_short Filter selection for indoor-recirculating fan-coil unit respect to indoor-to-outdoor particle relationships and occupancy influences
title_sort filter selection for indoor recirculating fan coil unit respect to indoor to outdoor particle relationships and occupancy influences
topic DRNTU::Engineering
url http://hdl.handle.net/10356/68468
work_keys_str_mv AT xuxiaoqian filterselectionforindoorrecirculatingfancoilunitrespecttoindoortooutdoorparticlerelationshipsandoccupancyinfluences