Summary: | Energy labelization is a project held by government of Indonesia to ingnitiate people
awarness of electrical energy consumption at daily life. It has produce standardization for
light bulb and certainly will be developed to another tools. For air conditioning machine
which has giant energy consumption, government has creating SNI : 19-6713-2002 as
guideline but it has not equipped with the design of its testing machine to testing and defining
electrical power used for the equipment.
As the system design created, the air conditioning machine performance testing system
is sized 8.5m length, 6.0m width, 3m height and consist of two major parts : indoor and
outdoor compartment, both has conditioning unit to creating cooling load of air conditioning
machine. Those system is calculating Energy Efficiency Ratio (EER), which as major
calculation of electricity needed by air conditioning machine to perform conditioning process.
Each conditioning unit is consist of : mixer + fan to mixing air and adding circulation
air, humidifier to conditioning humidity, electrical heater to increasing temperature, and
cooling coil to lowering temperature. Those instrumentation are controlled in control panel in
outside of machine and can be conditioned in several condition based on natural climate in
Indonesia (minimum temperature + maximum humidity, and maximum temperature +
minimum humidity, for about 5oC 98% - 39oC 20%). It also can accomodating maximum
cooling load of ordinary 2 PK (1470W) air conditioning machine. Fulfilling those design also
following its operational procedure, electricity used for air conditioning machine also its
energy efficiency ratio (EER) can be defined and energy labelization project can be optimised
and creating economical energy habitual in modern society.
|