PENGARUH HARMONIK TERHADAP PENURUNAN KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA DI POLITEKNIK NEGERI SEMARANG
The Semarang State Polytechnic as an institution of higher vocational education currently has more than 500 units computers which is spread out on 21 computer laboratories / multimedia laboratories. In each laboratory is equipped with air conditioner (AC). Power supply system in Polines is served by...
Main Authors: | , |
---|---|
Format: | Thesis |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2012
|
Subjects: |
_version_ | 1826045650394939392 |
---|---|
author | , Akhmad Jamaah , Dr. Eng. F. Danang Wijaya, S.T., M.T. |
author_facet | , Akhmad Jamaah , Dr. Eng. F. Danang Wijaya, S.T., M.T. |
author_sort | , Akhmad Jamaah |
collection | UGM |
description | The Semarang State Polytechnic as an institution of higher vocational education
currently has more than 500 units computers which is spread out on 21 computer
laboratories / multimedia laboratories. In each laboratory is equipped with air conditioner
(AC). Power supply system in Polines is served by 2 transformers, named transformer
transformer III and transformer I . The power capacity of transformer III and transformer
I are 400 kVA .
Computer, printer, energy-efficient lighting and other appliances with motor
speed control are a non-linear loads that cause harmonics in the power system network.
High content of harmonics on power system network causes overheating to the
distribution transformers. It is not treated immediately will cause the transformer life time
becomes shorter.
The research was aimed to determine harmonics content and its effect on
distribution transformers in Polines by performing measurements on transformers under
load conditions. The transformers load was in accordance with the required of Polines
load in academic and administrativ activities. The comparation method between the
results of measurements with the IEEE 519-1992 standard is used to analyze the
problem. By comparing the measurement results with the IEEE 519-1992 standard, it can
be determined whether the tranformer need to be derating or not.
Based on the results of the research, the harmonic content of the transformer III
and transformer I for the total harmonic content of voltage (THDV) was below the
standard (<5%) and total harmonic current content (TDD) or IHD for the second
transformer was also below the standard. So that the transformers did not need for
derating. However, due to the fact that transformer was over heated, it means that the heat
of the transformer has gone beyond that allowed by the standard heat SPLN 8-2: 1991,
then it needs to be calculated transformer losses increase due to load containing
harmonics.
The results of the research indicate that, the harmonic content transformer
III for the TDD and IHD were higher than the transformer I, this causes higher
heating effect. The highest temperature for transformer III was 67.5 °C, while the
transformer I was 66.2 oC. |
first_indexed | 2024-03-13T22:40:22Z |
format | Thesis |
id | oai:generic.eprints.org:99837 |
institution | Universiti Gadjah Mada |
last_indexed | 2024-03-13T22:40:22Z |
publishDate | 2012 |
publisher | [Yogyakarta] : Universitas Gadjah Mada |
record_format | dspace |
spelling | oai:generic.eprints.org:998372016-03-04T08:45:33Z https://repository.ugm.ac.id/99837/ PENGARUH HARMONIK TERHADAP PENURUNAN KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA DI POLITEKNIK NEGERI SEMARANG , Akhmad Jamaah , Dr. Eng. F. Danang Wijaya, S.T., M.T. ETD The Semarang State Polytechnic as an institution of higher vocational education currently has more than 500 units computers which is spread out on 21 computer laboratories / multimedia laboratories. In each laboratory is equipped with air conditioner (AC). Power supply system in Polines is served by 2 transformers, named transformer transformer III and transformer I . The power capacity of transformer III and transformer I are 400 kVA . Computer, printer, energy-efficient lighting and other appliances with motor speed control are a non-linear loads that cause harmonics in the power system network. High content of harmonics on power system network causes overheating to the distribution transformers. It is not treated immediately will cause the transformer life time becomes shorter. The research was aimed to determine harmonics content and its effect on distribution transformers in Polines by performing measurements on transformers under load conditions. The transformers load was in accordance with the required of Polines load in academic and administrativ activities. The comparation method between the results of measurements with the IEEE 519-1992 standard is used to analyze the problem. By comparing the measurement results with the IEEE 519-1992 standard, it can be determined whether the tranformer need to be derating or not. Based on the results of the research, the harmonic content of the transformer III and transformer I for the total harmonic content of voltage (THDV) was below the standard (<5%) and total harmonic current content (TDD) or IHD for the second transformer was also below the standard. So that the transformers did not need for derating. However, due to the fact that transformer was over heated, it means that the heat of the transformer has gone beyond that allowed by the standard heat SPLN 8-2: 1991, then it needs to be calculated transformer losses increase due to load containing harmonics. The results of the research indicate that, the harmonic content transformer III for the TDD and IHD were higher than the transformer I, this causes higher heating effect. The highest temperature for transformer III was 67.5 °C, while the transformer I was 66.2 oC. [Yogyakarta] : Universitas Gadjah Mada 2012 Thesis NonPeerReviewed , Akhmad Jamaah and , Dr. Eng. F. Danang Wijaya, S.T., M.T. (2012) PENGARUH HARMONIK TERHADAP PENURUNAN KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA DI POLITEKNIK NEGERI SEMARANG. UNSPECIFIED thesis, UNSPECIFIED. http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=56046 |
spellingShingle | ETD , Akhmad Jamaah , Dr. Eng. F. Danang Wijaya, S.T., M.T. PENGARUH HARMONIK TERHADAP PENURUNAN KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA DI POLITEKNIK NEGERI SEMARANG |
title | PENGARUH HARMONIK TERHADAP PENURUNAN
KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA
DI POLITEKNIK NEGERI SEMARANG |
title_full | PENGARUH HARMONIK TERHADAP PENURUNAN
KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA
DI POLITEKNIK NEGERI SEMARANG |
title_fullStr | PENGARUH HARMONIK TERHADAP PENURUNAN
KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA
DI POLITEKNIK NEGERI SEMARANG |
title_full_unstemmed | PENGARUH HARMONIK TERHADAP PENURUNAN
KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA
DI POLITEKNIK NEGERI SEMARANG |
title_short | PENGARUH HARMONIK TERHADAP PENURUNAN
KAPASITAS DAYA TRAFO DISTRIBUSI 400 kVA
DI POLITEKNIK NEGERI SEMARANG |
title_sort | pengaruh harmonik terhadap penurunan kapasitas daya trafo distribusi 400 kva di politeknik negeri semarang |
topic | ETD |
work_keys_str_mv | AT akhmadjamaah pengaruhharmonikterhadappenurunankapasitasdayatrafodistribusi400kvadipolitekniknegerisemarang AT drengfdanangwijayastmt pengaruhharmonikterhadappenurunankapasitasdayatrafodistribusi400kvadipolitekniknegerisemarang |