Method of Calculation of Current of the Ground Faults in the Parallel Overhead Transmission Lines 110-220 Kv
The mutual induction between the phase wires of the different overhead lines which situate close to each other cause unbalanced redistribution of currents in the line wires. This leads to emergence of the outof-balance zero sequence current which affects negatively on the sensitivity of the zero-seq...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
EDP Sciences
2017-01-01
|
Series: | MATEC Web of Conferences |
Online Access: | http://dx.doi.org/10.1051/matecconf/20179101021 |