Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia
The trip-out rates calculated by taking account of the reduction in the tower-footing resistance due to the ionizing effect agree well with the observed ones. This indicates the importance of the impulse resistance in the analysis of the lightning performance of the line. The trip-out rate at the lo...