Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia
The trip-out rates calculated by taking account of the reduction in the tower-footing resistance due to the ionizing effect agree well with the observed ones. This indicates the importance of the impulse resistance in the analysis of the lightning performance of the line. The trip-out rate at the lo...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
EDP Sciences
2018-01-01
|
Series: | MATEC Web of Conferences |
Online Access: | https://doi.org/10.1051/matecconf/201821501022 |
_version_ | 1829519307525062656 |
---|---|
author | Warmi Yusreni Michishita Koji |
author_facet | Warmi Yusreni Michishita Koji |
author_sort | Warmi Yusreni |
collection | DOAJ |
description | The trip-out rates calculated by taking account of the reduction in the tower-footing resistance due to the ionizing effect agree well with the observed ones. This indicates the importance of the impulse resistance in the analysis of the lightning performance of the line. The trip-out rate at the lower arm is high for the cases of the average grounding resistance of 33.3 ohms, and the rates at the upper arm are high for the cases of the average grounding resistance of 5.6 ohms. Such à trend can be simulated by the IEEE method using the impulse resistance. The trend for the trip-out ratio to become high with the increase in the span length is significant after improvement of the tower-footing resistance. However, the trend is weak before improvement of the tower-footing resistance. This is because in the case of the high tower-footing resistance the flashover occurs before the arrival of the wave reflected from the adjacent towers due to the high potential rise of the tower. Therefore, the degree of the influence of the span length on the trip-out ratio is dependent on the tower-footing resistance. The local lightning activity significantly affects the trip-out rate. |
first_indexed | 2024-12-16T14:37:05Z |
format | Article |
id | doaj.art-4a6528a95be04beca41f96c5e318136f |
institution | Directory Open Access Journal |
issn | 2261-236X |
language | English |
last_indexed | 2024-12-16T14:37:05Z |
publishDate | 2018-01-01 |
publisher | EDP Sciences |
record_format | Article |
series | MATEC Web of Conferences |
spelling | doaj.art-4a6528a95be04beca41f96c5e318136f2022-12-21T22:28:03ZengEDP SciencesMATEC Web of Conferences2261-236X2018-01-012150102210.1051/matecconf/201821501022matecconf_ictis2018_01022Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in IndonesiaWarmi Yusreni0Michishita Koji1Padang Institute of TechnologyGraduate School of Science and Technology, Shizuoka UniversityThe trip-out rates calculated by taking account of the reduction in the tower-footing resistance due to the ionizing effect agree well with the observed ones. This indicates the importance of the impulse resistance in the analysis of the lightning performance of the line. The trip-out rate at the lower arm is high for the cases of the average grounding resistance of 33.3 ohms, and the rates at the upper arm are high for the cases of the average grounding resistance of 5.6 ohms. Such à trend can be simulated by the IEEE method using the impulse resistance. The trend for the trip-out ratio to become high with the increase in the span length is significant after improvement of the tower-footing resistance. However, the trend is weak before improvement of the tower-footing resistance. This is because in the case of the high tower-footing resistance the flashover occurs before the arrival of the wave reflected from the adjacent towers due to the high potential rise of the tower. Therefore, the degree of the influence of the span length on the trip-out ratio is dependent on the tower-footing resistance. The local lightning activity significantly affects the trip-out rate.https://doi.org/10.1051/matecconf/201821501022 |
spellingShingle | Warmi Yusreni Michishita Koji Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia MATEC Web of Conferences |
title | Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia |
title_full | Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia |
title_fullStr | Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia |
title_full_unstemmed | Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia |
title_short | Tower-Footing Resistance and Lightning Trip-outs of 150 kV Transmission Lines in West Sumatra in Indonesia |
title_sort | tower footing resistance and lightning trip outs of 150 kv transmission lines in west sumatra in indonesia |
url | https://doi.org/10.1051/matecconf/201821501022 |
work_keys_str_mv | AT warmiyusreni towerfootingresistanceandlightningtripoutsof150kvtransmissionlinesinwestsumatrainindonesia AT michishitakoji towerfootingresistanceandlightningtripoutsof150kvtransmissionlinesinwestsumatrainindonesia |