The correction of instrument transformer ferroresonance model in IEC standard and study on resonance interval based on transformer damping
The traditional ferromagnetic resonance model of the inductive voltage transformer in the IEC/TR 61869-102 transformer standard ignores the DC resistance of the transformer. The author believes that ignoring the damping effect of the transformer itself is not justified. Based on this, the model is m...