Partial discharge calibrator of a cavity inside high-voltage insulator

This article displayed the method of partial discharge (PD) measurement in high-voltage insulator and calibrating the effective element (capacitor) to enhance the PD signal. The cavity shapes were plate–plate, cylindrical and spherical inside the solid insulator. The proposed system enables from det...

Full description

Bibliographic Details
Main Authors: Hamoodi Ali N., Hamoodi Safwan A., Mohammed Rasha A.
Format: Article
Language:English
Published: De Gruyter 2022-07-01
Series:Open Engineering
Subjects:
Online Access:https://doi.org/10.1515/eng-2022-0048